Copyr ght Copyrght Trdonc GmbH & Co KG All rghts reserved. Manufactur er Trdonc GmbH & Co KG Färbergasse 15 6851 Dornbrn Austra Tel. +43-(0)5572-395-0 Fax +43-(0)5572-20176 www.trdonc.com Document number
Table of contents 1 How to use ths manual...4 2 Safety nstr uctons...5 3 Devce descr pton...6 3.1 Applcaton...7 area 3.2 Operatng...7 modes 3.3 Acoustc...8 sgnals 4 Pr oject desgn...9 5 Commssonng...12 5.1 Startng...13 commssonng 5.2 Groupng...15 lumnares 5.3 Fnshng...16 commssonng 6 Savng scenes...17 7 Regr oupng lumnar es...18 8 Oper aton 8.1 9 10...21 Changng...21 ntensty 8.1.1 Sngle momentary-acton...21 swtch control 8.1.2 Double momentary-acton...22 swtch control 8.2 Changng...23 colour temperature 8.3 Recallng...23 scenes System extenson...24 9.1 Startng...24 system extenson 9.2 Addng or...26 changng lumnares 9.3 Addng or...27 changng DALI XC devces 9.4 Fnshng...28 system extenson Techncal data...29 3
How to use ths manual 1 How to use ths manual We are pleased that you have chosen ths Trdonc GmbH & Co KG product. So that you can get the most from ths manual, the followng nformaton wll be set out n ths secton: Characters and symbols n ths manual Further nformaton These commssonng nstructons descrbe how to use the DALI XC n the comfortdim system. Characters and symbols n ths manual The followng characters and symbols are used n ths manual: Character/ symbol Descrpton 1. Indvdual steps n the nstructons are numbered. Sngle-step nstructons are ndcated by at the begnnng of the lne. After a step has been descrbed, a descrpton of the expected results wll follow. These results are ndcated by at the begnnng of the lne. Requrements whch need to be checked before carryng out a step are ndcated by. s can be recognsed by. In addton, notes are dentfed by the word. Table 1: Characters and symbols n ths manual Further nformaton More nformaton on nstallng the DALI XC can be found n the nstallaton nstructons suppled wth the devce. General nformaton on our products can be found on our webste: www.trdonc.com 4
Safety nstructons 2 Safety nstructons The devce may only be used for the applcaton area specfed. Relevant health and safety regulatons must be observed. When assemblng and nstallng the devce, the voltage supply must be dsconnected. Only qualfed personnel may assemble, nstall and commsson the devce. If an error occurs, dangerous voltage levels may be present at the DALI termnals and on the DALI control lne. 5
Devce descrpton 3 Devce descrpton Fgure 1: DALI XC nput devce (1) Termnals (2) "Confg" rotary selector swtch (3) "Mode" rotary selector swtch 6
Devce descrpton 3.1 Applcaton area The DALI XC s a devce wth four nputs for controllng lghtng wth sngle momentary-acton swtches, double momentary-acton swtches and standard swtches, whch can be combned n some operatng modes. The DALI XC s suppled by the DALI control lne. For ths reason, a devce that provdes the voltage supply s requred for use n a lghtng system (e.g. DALI PS2). Fgure 2: DALI XC n a lghtng system as part of the comfortdim system 3.2 Operatng modes The Mode rotary selector swtch s used to set the operatng mode. Every letter A G on the Mode rotary selector swtch stands for an operatng mode specfed on the devce. If the rotary selector swtch s not turned to a marked poston, the DALI XC wll not functon. "MC" operatng mode Rotary selector swtch poston A Sngle momentary-acton swtches and/or double momentary-acton swtches and/or standard swtches can be used to recall programmed functons. The MC operatng mode can only be confgured usng the masterconfigurator software versons 2.10 and hgher. The devce does not functon n MC operatng mode by default. More nformaton can be found n the masterconfigurator software user manual nstalled wth the software. The user manual can also be downloaded from the Trdonc webste. A DALI XC devce n MC operatng mode can replace the DALI MC (art. No 86458507). "SC-A" operatng mode Rotary selector swtch poston B Sngle momentary-acton swtches can be used to recall scenes. No scenes can be saved n ths operatng mode. A DALI XC devce n SC-A operatng mode can replace the DALI SC-A (art. No 24138906). 7
Devce descrpton "SC" operatng mode Rotary selector swtch poston C Sngle momentary-acton swtches can be used to recall and save scenes. A DALI XC devce n SC operatng mode can replace the DALI SC (art. No 24034263). "GC-A" operatng mode Rotary selector swtch poston D Sngle momentary-acton swtches and/or double momentary-acton swtches can be used to swtch lumnare groups on/off and brghten or dm them. Programmng mode cannot be enabled n the operatng mode. If the lghtng system s swtched to programmng mode usng another DALI XC devce, the momentary-acton swtches connected to the DALI XC n GC-A operatng mode can be used to group lumnares. A DALI XC devce n GC-A operatng mode can replace the DALI GC-A (art. No 24138907). "GC" operatng mode Rotary selector swtch poston E Sngle momentary-acton swtches and/or double momentary-acton swtches can be used to swtch lumnare groups on/off and brghten or dm them. A system extenson s typcally started n ths operatng mode. If the lghtng system s n programmng mode, the momentary-acton swtches connected to the DALI XC n GC operatng mode can be used to group lumnares. A DALI XC devce n GC operatng mode can replace the DALI GC (art. No 24033450). "Prog" operatng mode Rotary selector swtch poston F Commssonng or a system extenson can be started and completed n ths operatng mode. The lghtng system s n programmng mode whle these processes are ongong. "TuWh" operatng mode Rotary selector swtch poston G Double momentary-acton swtches can be used to set the ntensty and colour temperature of Tunable Whte lumnares. 3.3 Acoustc sgnals Some actons on the DALI XC elct a dfferent number of hgh beeps. Durng confguraton, beepng ndcates that some steps have been reached. The DALI XC beeps three tmes when the voltage supply has been establshed. In programmng mode, the DALI XC beeps once each tme a momentary-acton swtch s pressed. The DALI XC beeps once, twce or three tmes after varous confguraton steps. The DALI XC beeps once after approx. 1 s when one of the rotary selector swtches s turned to a new poston. 8
Project desgn 4 Project desgn The followng condtons apply for the project desgn of a lghtng system wth DALI XC: No more than 64 DALI-compatble control gear elements can be used. No more than 16 groups can be confgured. A lumnare can be assgned to max. 16 groups. No more than 16 scenes can be confgured. The maxmum number of DALI XC devces that can be used n a lghtng system depends on the total power consumpton of the devces connected to the DALI control lne. The power consumpton of the ndvdual devces can be found n the assocated data sheets. The followng nformaton apples to the use of the DALI XC n the comfortdim system. Assgnng groups to nputs (DALI XC n "GC-A" or "GC" operatng mode) Rotary selector swtch poston D or E The Confg rotary selector swtch s used to assgn dfferent groups to nput T1 and T2 and nput T3 and T4. The followng table uses the rotary selector swtch poston to ndcate whch group s assgned to the nputs. Rotary selector swtch poston Group Input T1 and T2 Input T3 and T4 0 all 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 9 9 9 10 10 10 11 11 11 12 12 12 13 13 13 14 14 14 15 15 15 16 Table 2: Assgnng groups to nputs (DALI XC n "GC-A" or "GC" operatng mode) 9
Project desgn Assgnng groups to nputs (DALI XC n "TuWh" operatng mode) Rotary selector swtch poston G The Confg rotary selector swtch s used to assgn a group to all nputs. The ntensty of the group can be changed wth nput T1 and T2 and the colour temperature of Tunable Whte lumnares n the group can be changed wth nput T3 and T4. The followng table uses the rotary selector swtch poston to ndcate whch group s assgned to the DALI XC. Rotary selector swtch poston Group 0 all 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 9 9 10 10 11 11 12 12 13 13 14 14 15 15 Table 3: Assgnng groups (DALI XC n "TuWh" operatng mode) 10
Project desgn Assgnng scenes to nputs (DALI XC n "SC-A" or "SC" operatng mode) Rotary selector swtch poston B or C The Confg rotary selector swtch s used to assgn dfferent scenes to nputs T1 T4. The followng table uses the rotary selector swtch poston to ndcate whch scene s assgned to the nputs. Rotary selector swtch poston Scene Input T1 Input T2 Input T3 Input T4 0 1 2 3 4 1 2 3 4 5 2 3 4 5 6 3 4 5 6 7 4 5 6 7 8 5 6 7 8 9 6 7 8 9 10 7 8 9 10 11 8 9 10 11 12 9 10 11 12 13 10 11 12 13 14 11 12 13 14 15 12 13 14 15 16 13 14 15 16 1 14 15 16 1 2 15 16 1 2 3 Table 4: Assgnng scenes to nputs (DALI XC n "SC-A" or "SC" operatng mode) 11
Commssonng 5 Commssonng Requrement: Lghtng system must have been fully nstalled. A DALI XC n Prog operatng mode s desgned for commssonng a lghtng system. However, f all DALI XC devces n the lghtng system are already nstalled and can no longer be accessed, a DALI XC n GC operatng mode can be used to commsson the system. Ths procedure s useful for cases where the lghtng system needs to be re-ntalsed. After commssonng, the Mode rotary selector swtch s used to swtch the DALI XC from Prog operatng mode to another mode so that t can be operated as an nput devce. The devce must be accessble n the concealed box for ths to take place. Alternatvely, a DALI XC devce can be connected to the DALI control lne at an accessble pont (e.g. the dstrbuton board) for commssonng purposes only. Commssonng conssts of three steps: 1. Start commssonng. If the DALI XC devces n the lghtng system can be accessed, commssonng can be quckly and easly started wth a DALI XC n Prog operatng mode. If the DALI XC devces n the lghtng system can no longer be accessed, commssonng can be started wth a DALI XC n GC operatng mode. 2. Group lumnares. Frst select the lumnare to be grouped. Ths lumnare s then assgned to a group usng a momentary-acton swtch. 3. Fnsh commssonng. 12
Commssonng 5.1 Startng commssonng Startng commssonng wth DALI XC n "Prog" operatng mode Exstng assgnments of lumnares to groups are deleted. Startng may take several mnutes dependng on the number of connected lumnares. 1. Hold down momentary-acton swtch (approx. 10 s). 2 beeps sound at the begnnng. 3 beeps sound after another 10 s. 2. Release momentary-acton swtch. Assgnment of all lumnares to groups has been deleted. Programmng mode s enabled. All lumnares are dmmed to the mnmum value. All lumnares are brghtened one after the other. All lumnares are then dmmed to the mnmum value agan. 1 beep sounds. One lumnare brghtens. Fgure 3: Startng commssonng (DALI XC n "Prog" operatng mode) 13
Commssonng Startng commssonng wth DALI XC n "GC" operatng mode Exstng assgnments of lumnares to groups are deleted. Startng may take several mnutes dependng on the number of connected lumnares. 1. Hold down momentary-acton swtch (approx. 10 s). 1 beep sounds. 2. Release momentary-acton swtch. 1 beep sounds. 3. Hold down momentary-acton swtch (approx. 3 s). 2 beeps sound after 1 s. 3 beeps sound after another 2 s. 4. Release momentary-acton swtch. Assgnment of all lumnares to groups has been deleted. Programmng mode s enabled. All lumnares are dmmed to the mnmum value. All lumnares are brghtened one after the other. All lumnares are then dmmed to the mnmum value agan. 1 beep sounds. One lumnare brghtens. Fgure 4: Startng commssonng (DALI XC n "GC" operatng mode) 14
Commssonng 5.2 Groupng lumnares Requrement: Programmng mode must have been started. In programmng mode: The lumnare that s brght s the one that s currently selected. Lumnares can be selected usng any momentary-acton swtch on any DALI XC n operatng mode GC-A and GC. Brefly pressng a momentary-acton swtch selects lumnares one after the other. When the last lumnare s selected, the frst lumnare s selected agan n the next step. The DALI XC beeps once every tme a momentary-acton swtch s pressed. 1. Use a momentary-acton swtch to select the desred lumnare. Lumnare brghtens. From now on, use the momentary-acton swtch to whch the desred group s assgned. Secton Project desgn descrbes how to determne whch group s assgned to whch nput. Go to Secton "Project desgn"... 9 2. Hold down momentary-acton swtch (approx. 3 s). 1 beep sounds. 3. Release momentary-acton swtch. Selected lumnare s assgned to the desred group. Fgure 5: Assgnng a lumnare to a group A lumnare can be assgned to more than one group. Tunable Whte lumnares and normal lumnares can be assgned to the same group. 15
Commssonng 5.3 Fnshng commssonng 1. Hold down momentary-acton swtch (approx. 10 s). 1 beep sounds after 3 s. 1 beep sounds after another 3 s. 3 beeps sound after another 4 s. 2. Release momentary-acton swtch. Programmng mode s termnated. System s ready agan. Fgure 6: Fnshng commssonng If no momentary-acton swtches are pressed for 10 mnutes n programmng mode, ths mode s automatcally termnated. 16
Savng scenes 6 Savng scenes Scenes can only be saved wth a DALI XC n SC operatng mode. Requrement: Lghtng must be set to the desred values. Secton Operaton descrbes how to set the lghtng usng a DALI XC. Go to Secton "Operaton"... 21 From now on, use the momentary-acton swtch to whch the desred scene s assgned. Secton Project desgn descrbes how to determne whch scene s assgned to whch nput. Go to Secton "Project desgn"... 9 1. Hold down momentary-acton swtch (approx. 10 s). 1 beep sounds. 2. Release momentary-acton swtch. 2 beeps sound. The current ntenstes and colour temperature values for all lumnares are saved as a scene. or 2. Hold down the momentary-acton swtch for longer than 2 s. No values are saved for the scene. Fgure 7: Savng a scene 17
Regroupng lumnares 7 Regroupng lumnares Groupng can only be carred out wth DALI XC devces n GC-A or GC operatng mode. Regroupng refers to one of two cases: 1. Regroup ndvdual lumnares. If a lumnare that s already assgned to one group s added to another group, the lumnare s then assgned to both groups. To change the assgnment,.e. move a lumnare from one group to another, the exstng assgnment must frst be deleted and the lumnare must then be reassgned to the desred group. Ths process s descrbed n ths secton. 2. Regroup all lumnares (re-ntalsaton). If more than one lumnare must be regrouped, t may be more effcent to delete all assgnments frst and then reassgn all lumnares to the desred groups. Ths process s descrbed n Secton Commssonng. Go to Secton "Commssonng"... 12 18
Regroupng lumnares Deletng a lumnare from a group Requrement: System extenson must have been started. Secton Startng system extenson descrbes how to start the system extenson. Go to Secton "Startng system extenson"... 24 In programmng mode: The lumnare that s brght s the one that s currently selected. Lumnares can be selected usng any momentary-acton swtch on any DALI XC n operatng mode GC-A and GC. Brefly pressng a momentary-acton swtch selects lumnares one after the other. When the last lumnare s selected, the frst lumnare s selected agan n the next step. The DALI XC beeps once every tme a momentary-acton swtch s pressed. 1. Use a momentary-acton swtch to select the desred lumnare. Lumnare brghtens. From now on, use the momentary-acton swtch to whch the desred group s assgned. Secton Project desgn descrbes how to determne whch group s assgned to whch nput. Go to Secton "Project desgn"... 9 2. Hold down momentary-acton swtch (approx. 6 s). 1 beep sounds after 3 s. 1 beep sounds after another 3 s. 3. Release momentary-acton swtch. Selected lumnare s deleted from the desred group. Lumnare remans selected. Fgure 8: Deletng a lumnare from a group 19
Regroupng lumnares Groupng lumnare From now on, use the momentary-acton swtch to whch the desred group s assgned. Secton Project desgn descrbes how to determne whch group s assgned to whch nput. Go to Secton "Project desgn"... 9 4. Hold down momentary-acton swtch (approx. 3 s). 1 beep sounds. 5. Release momentary-acton swtch. Selected lumnare s assgned to the desred group. Fgure 9: Assgnng a lumnare to a group A lumnare can be assgned to more than one group. Tunable Whte lumnares and normal lumnares can be assgned to the same group. 6. Fnsh system extenson. 20
Operaton 8 Operaton Dependng on whch operatng mode t s n, the DALI XC can be used to operate lumnares n the followng ways: Swtch lumnare groups on and off Brghten and dm lumnare groups Increase and decrease the colour temperature of Tunable Whte lumnares n a lumnare group Recall scenes 8.1 Changng ntensty The Confg rotary selector swtch s used to assgn dfferent groups to the DALI XC nputs. Secton Project desgn descrbes whch group s assgned to the nputs. Go to Secton "Project desgn"... 9 8.1.1 Sngle momentary-acton swtch control Requrement: DALI XC must be n GC-A or GC operatng mode. Swtchng lghtng on and off Brefly press sngle momentary-acton swtch. The group assgned to the momentary-acton swtch s swtched on and off n alternatng sequence each tme the momentary-acton swtch s pressed. Brghtenng and dmmng lghtng Hold down the sngle momentary-acton swtch. The group assgned to the momentary-acton swtch s brghtened and dmmed n alternatng sequence each tme the momentary-acton swtch s pressed. 21
Operaton 8.1.2 Double momentary-acton swtch control Requrement: DALI XC must be n GC-A, GC or TuWh operatng mode. If the DALI XC s n TuWh operatng mode, the ntensty of the assgned group can only be changed wth the double momentary-acton swtch connected to nput T1 and T2. Swtchng on lghtng Brefly press double momentary-acton swtch. The group assgned to the momentary-acton swtch s swtched on. The colour temperature of the Tunable Whte lumnares n the group s set to the last saved value. Swtchng off lghtng Brefly press double momentary-acton swtch. The group assgned to the momentary-acton swtch s swtched off. Brghtenng lghtng Hold down double momentary-acton swtch. The group assgned to the momentary-acton swtch s brghtened. The colour temperature of the Tunable Whte lumnares n the assgned group stays the same. Dmmng lghtng Hold down double momentary-acton swtch. The group assgned to the momentary-acton swtch s dmmed. The colour temperature of the Tunable Whte lumnares n the assgned group stays the same. 22
Operaton 8.2 Changng colour temperature The Confg rotary selector swtch s used to assgn dfferent groups to the DALI XC nputs. Secton Project desgn descrbes whch group s assgned to the nputs. Go to Secton "Project desgn"... 9 Requrement: DALI XC must be n TuWh operatng mode. The colour temperature of Tunable Whte lumnares n the group can only be changed usng the double momentary-acton swtch at nput T3 and T4. A low colour temperature s perceved as warm whte lght. In contrast a hgh colour temperature s perceved as cool whte lght. Reducng the colour temperature Hold down double momentary-acton swtch. The colour temperature of the Tunable Whte lumnares n the assgned group s contnually decreased. or Brefly press double momentary-acton swtch. The colour temperature of the Tunable Whte lumnares n the assgned group s decreased by one ncrement. Increasng the colour temperature Hold down double momentary-acton swtch. The colour temperature of the Tunable Whte lumnares n the assgned group s contnually ncreased. or Brefly press double momentary-acton swtch. The colour temperature of the Tunable Whte lumnares n the assgned group s ncreased by one ncrement. 8.3 Recallng scenes The Confg rotary selector swtch s used to assgn dfferent scenes to nputs T1 T4. Secton Project desgn descrbes whch scene s assgned to the nputs. Go to Secton "Project desgn"... 9 Requrement: DALI XC must be n SC-A or SC operatng mode. Brefly press sngle momentary-acton swtch. The scene assgned to the momentary-acton swtch s recalled. 23
System extenson 9 System extenson If lumnares or DALI XC devces are added or changed n the lghtng system, these devces can be ncorporated nto the controls usng a system extenson. If the DALI XC devces n the lghtng system can be easly accessed, the system extenson can be quckly and easly started wth a DALI XC n Prog operatng mode. If the DALI XC devces n the lghtng system can no longer be accessed, the system extenson can be started wth a DALI XC n GC operatng mode. 9.1 Startng system extenson Startng system extenson wth DALI XC n "Prog" operatng mode Brefly press momentary-acton swtch. 2 beeps sound. Programmng mode s enabled. All lumnares are dmmed to the mnmum value. All lumnares are brghtened one after the other. All lumnares are then dmmed to the mnmum value agan. 1 beep sounds. One lumnare brghtens. Fgure 10: Startng system extenson (DALI XC n "Prog" operatng mode) 24
System extenson Startng system extenson wth DALI XC n "GC" operatng mode 1. Hold down momentary-acton swtch (approx. 10 s). 1 beep sounds. 2. Release momentary-acton swtch. 1 beep sounds. 3. Hold down momentary-acton swtch (approx. 1 s). 2 beeps sound. 4. Release momentary-acton swtch. Programmng mode s enabled. All lumnares are dmmed to the mnmum value. All lumnares are brghtened one after the other. All lumnares are then dmmed to the mnmum value agan. 1 beep sounds. One lumnare brghtens. Fgure 11: Startng system extenson (DALI XC n "GC" operatng mode) 25
System extenson 9.2 Addng or changng lumnares 1. Dsconnect the voltage supply to the lghtng system. 2. To change a lumnare, proceed as follows: Remove the old lumnare. 3. Install the new lumnare n accordance wth the accompanyng nstallaton nstructons. 4. Reconnect the voltage supply. 5. Start system extenson. Updated lghtng system data s saved to all DALI XC devces. In programmng mode: The lumnare that s brght s the one that s currently selected. Lumnares can be selected usng any momentary-acton swtch on any DALI XC n operatng mode GC-A and GC. Brefly pressng a momentary-acton swtch selects lumnares one after the other. When the last lumnare s selected, the frst lumnare s selected agan n the next step. The DALI XC beeps once every tme a momentary-acton swtch s pressed. 6. Use a momentary-acton swtch to select the new lumnare. Lumnare brghtens. From now on, use the momentary-acton swtch to whch the desred group s assgned. Secton Project desgn descrbes how to determne whch group s assgned to whch nput. Go to Secton "Project desgn"... 9 7. Hold down momentary-acton swtch (approx. 3 s). 1 beep sounds. 8. Release momentary-acton swtch. Selected lumnare s assgned to the desred group. 9. Fnsh system extenson. Adjustng scenes Secton Savng scenes descrbes how to set and save values for scenes. Go to Secton "Savng scenes"... 17 Carry out the followng steps for each scene contanng the new lumnare. 1. Recall the scene. 2. Set the values agan. 3. Save the scene. 26
System extenson 9.3 Addng or changng DALI XC devces 1. Dsconnect the voltage supply to the lghtng system. 2. To change a DALI XC devce, proceed as follows: Remove the old DALI XC. 3. Install the new DALI XC n accordance wth the accompanyng nstallaton nstructons. 4. Set the Mode and Confg rotary selector swtch postons to match the old DALI XC or as desred. 5. Reconnect the voltage supply. 6. Start system extenson. Lumnare assgnment to groups s saved n the new DALI XC devce. 1 beep sounds. Lumnare brghtens. 7. Fnsh system extenson. Testng settngs Secton Changng ntensty descrbes how to change the ntensty. Go to Secton "Changng ntensty"... 21 Secton Changng colour temperature descrbes how to change the colour temperature. Go to Secton "Changng colour temperature"... 23 Secton Recallng scenes descrbes how to recall scenes. Go to Secton "Recallng scenes"... 23 Change the ntensty f the devce s n GC-A or GC operatng mode. or Change ntensty and colour temperature f the devce s n TuWh operatng mode. or Recall scenes f the devce s n SC-A or SC operatng mode. Adjustng settngs The user manual for the masterconfigurator software verson 2.10 or hgher descrbes how to confgure the MC operatng mode. Reprogram functons f the devce s n MC operatng mode. 27
System extenson 9.4 Fnshng system extenson 1. Hold down momentary-acton swtch (approx. 10 s). 1 beep sounds after 3 s. 1 beep sounds after another 3 s. 3 beeps sound after another 4 s. 2. Release momentary-acton swtch. Programmng mode s termnated. System s ready agan. Fgure 12: Fnshng system extenson If no momentary-acton swtches are pressed for 10 mnutes n programmng mode, ths mode s automatcally termnated. 28
Techncal data 10 Techncal data Supply Va DALI control lne Power consumpton Max. 6 ma Bus loads Max. 3 Inputs 4 nputs (T1 T4) Interface DALI control lne (DA, DA) Termnals 0.5 1.5 mm² (sold or fne-stranded) Degree of protecton IP20 Housng materal Polycarbonate (PC), flame-retardant, halogen-free Installaton In concealed box: 60 x 61 (Ø x D, n mm) Dmensons 47.7 x 28.2 x 14.6 (W x H x D, n mm) Permssble ambent temperature 0 60 C Permssble relatve humdty 20 90%, non-condensng Weght Approx. 12 g Table 5: DALI XC techncal data 29